1. Output rated voltage: see Table 3
2. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
3. Load capacity: 0.1Hz maximum 1.1µF
0.05Hz max 2.2µF
0.02Hz maximum 5.5µF
4. Measurement accuracy: 3%
5. Voltage positive and negative peak error: ≤3%
6. Voltage waveform distortion: ≤5%
7. Conditions of use: indoors and outdoors; temperature: -10℃~+40℃; humidity: ≤85%RH
8. Power fuse: see table 3
9. Power supply: voltage 220V±5%, 50±5Hz
Note: If a portable generator is used for power supply, the generator output voltage and frequency are required to be stable (generally, the power is greater than 3kW, the frequency is 50Hz, and the voltage is 220V±5%)
10. The capacitance of the tested product shall not exceed the maximum value of the rated capacitance of the instrument, and the value is shown in Table 3;
model |
Rated voltage |
Load capacity |
power supply
Fuse
|
Product structure and weight |
30/1.1 |
30kV
(Peak) |
0.1Hz,≤1.1µF |
10A |
Controller:4㎏
Booster:20㎏ |
0.05Hz,≤2.2µF |
0.02Hz,≤5.5µF |
40/1.1 |
40kV
(Peak) |
0.1Hz,≤1.1µF |
10A |
Controlle:4㎏
Booster:20㎏ |
0.05Hz,≤2.2µF |
0.02Hz,≤5.5µF |
50/1.1 |
50kV
(Peak) |
0.1Hz,≤1.1µF |
15A |
Controller:4㎏
Booster:40㎏ |
0.05Hz,≤2.2µF |
0.02Hz,≤5.5µF |
60/1.1 |
60kV
(Peak |
0.1Hz,≤1.1µF |
15A |
Controller:4㎏
Booster:50㎏ |
0.05Hz,≤2.2µF |
0.02Hz,≤5.5µF |
80/1.1 |
80kV
(Peak) |
0.1Hz,≤1.1µF |
15A |
Controller:4㎏
Booster:50㎏ |
0.05Hz,≤2.2µF |
0.02Hz,≤5.5µF |
90/1.1 |
90kV
(Peak) |
0.1Hz,≤1.1µF |
15A |
Controller:4㎏
Booster:55㎏ |
0.05Hz,≤2.2µF |
0.02Hz,≤5.5µF |