Time: the inherent opening and closing time of the 12 fractures, the same period and the same period between phases.
Reclosing: closing-opening, opening-closing, opening-closing-closing process time of each fracture: one minute time, one close time,
Two-in-one time, gold short time, no current time value.
Bounce: the closing bounce time of each fracture, the number of bounces, the bounce process, and the bounce waveform;
The opening rebound amplitude of each fracture.
Speed: Just opening, just closing speed, maximum speed, time-travel characteristic curve.
Travel: total travel, open distance, over travel, overshoot travel, rebound amplitude.
Current: the opening and closing current values and current waveform diagrams of the opening and closing coils.
Operating voltage: DC0~280V/20A digital adjustable circuit breaker operating power is provided in the machine to automatically complete the low voltage operating test of the circuit breaker and measure the operating voltage value of the circuit breaker.