Three phase relay tester triphase microcomputer relay protection tester device 3-phase relay test set

share
WeChat
Sina Weibo
QQ
QQ space
Douban
Baidu Post Bar
LinkedIn
Detail

Section 1 main features

1.Meet all test requirements on site.The instrument hasstandard four phase voltage and three-phase current output. It can test notonly various traditional relays and protection devices, but also

various modernmicrocomputer protections, especially for transformer differential protectionand standby automatic switching device. The test is more convenient andperfect.

2.All kinds of technical indexes fully meet the standard of DL /t624-1997 "technical conditions for microcomputer based test device ofrelay protection" issued by the

Ministry of electric power.

3.Classic Windows XP operation interface, friendly man-machineinterface, easy and fast operation; high performance embedded industrialcontrol computer and 8.4 inch resolution 800 × 600 TFT true color display screen, can provide rich and intuitiveinformation,

including the current working state of the equipment and varioushelp information.

4.This Windows XP system has its own recovery function to avoid systemcrash caused by illegal

shutdown or misoperation.

5.Equipped with ultrathin industrial keyboard and photoelectric mouse,it can complete all kinds of

operations through keyboard or mouse just likeordinary PC.

6.The main control board adopts DSP + FPGA structure and 16 bit DACoutput. It can generate 2000

high density sine wave per week for fundamentalwave, which greatly improves the quality of

waveform and the accuracy of thetester.

7.The high fidelity linear power amplifier ensures the accuracy of smallcurrent and the stability of large

current.

8.USB interface is used to communicate with PC directly without anyconnecting line, so it is

convenient to use.

9. can be connected to laptop (optional) to run.Laptops and industrialcomputers use the same set of

software, so there is no need to relearn theoperation method.

10.Equipped with independent dedicated DC auxiliary voltage sourceoutput, the output voltage is

110V (1a), 220V (0.6A).It can be used for relaysor protection devices that need DC power supply.

11.It has the function of software self calibration, which avoidsopening the case to calibrate the

accuracy by adjusting the potentiometer, thusgreatly improving the stability of accuracy.

Section 2 technical parameters

1.    AC current source (3 *30A)

Single phase current output (RMS)

0 -- 30A / phase, accuracy:  0.2% ± 5mA

Three phase parallel output (RMS)

0 - 90A / three phase in  phase parallel output

Allowable working value of phase current for a long time (effective  value)

9.9A

Maximum output power per phase

300VA

Maximum output power of three phase parallel current

800VA

Maximum output allowable working time of triple parallel current

5s

frequency range

0 -- 1000Hz, accuracy  0.001Hz

Harmonic number

2--20second

phase

0--360The accuracy is 0.1 degree

2. DC current source

DC current output

0--± 10A / phase, accuracy: 0.5% ± 5mA

3. AC voltage source

Single phase voltage output (RMS)

0 -- 120V / phase, accuracy:  0.2% ± 5mv

Line voltage output (RMS)

0--240V

Phase voltage / line voltage output power

75VA/100VA

frequency range

0 -- 1000Hz, accuracy:  0.001Hz

Harmonic number

2--20second

phase

0--360Degree, accuracy: 0.1 degree

4. DC voltage source

Single phasevoltage output  amplitude

0--± 160V, accuracy: 0.5% ± 5mv

Output amplitude of line  voltage

0--320V

Phase voltage / line voltage output power

90VA/180VA

5. switching value terminal

Switch input terminal

8yes

Air contact

1 -- 20 mA, 24 V, internal  active output of the device

Potential reversal

Passive contact: low  resistance short circuit signal

Active contact: 0-250V DC

Switch output terminal

4 pairs, empty contacts, interruption capacity: DC:  0-30V/5A,AC:0-250V/5A

6. others

time frame

1ms -- 9999s, measuring accuracy: 1ms

Volume and weight of portable series single machine

Volume 335 x 168 x 270mm3, about 12.5kg

Power Supply

AC220V±10%,50/60Hz,10A

7.Working time of AC current

Working current<10A

working  hours≤60minute

20A>Working current≥10A

working  hours≤70S

30A>Working current≥20A

working  hours≤15S

Working current:30A

working hours≤5S


WhatsApp:+8613989109502